The ODC24A output module is used for controlling or switching DC loads of 5-200 VDC. Each module provides 4000 volts (transient) of optical isolation between the field devices and the control logic.
Typical uses and applications for DC output modules include switching the following loads:
- DC relays
- DC solenoids
- DC motor starters
- DC lamps or indicators
- PLC logicODC24A modules are not for use with Opto 22 brains.
One-second Surge |
5 A |
Operating Ambient Temperature |
-30 °C to 70 °C |
Isolation, Input-to-Output (Transient) |
4000 volts |
Turn-on Time |
100 µs |
Turn-off Time |
750 µs |
Output Voltage Drop Maximum Peak |
1.6 volts |
Module Specifications
|
UNITS |
ODC24A* |
Line voltage – max. |
VDC |
200 |
Operating voltage range |
VDC |
5–200 |
Current rating |
Amps Amps |
1 0.55 |
UL Motor Load rating |
Amps |
1 |
Off-state leakage @ max. voltage |
mA |
2 |
Logic voltage – nominal |
VDC |
24 |
Logic voltage range (Vcc) |
VDC |
18–32 |
Logic pickup voltage |
VDC |
18 |
Logic dropout voltage |
VDC |
1 |
Logic input current |
mA |
18 |
Control resistance |
Ohms |
2.2K |
ODC24A modules are not for use with Opto 22 brains.